Use a split core current transformer (CT) when you need to measure or monitor current in an existing installation and disconnecting the conductor to fit a conventional solid-core CT would be impractical or disruptive. Its hinged or separable core can be opened around an accessible conductor, making it useful for retrofits, temporary audits, and adding monitoring to operating equipment. It is suitable only when its current ratio, accuracy, output, aperture, insulation rating, and installation conditions match the application. If the system requires especially demanding measurement accuracy or the conductor cannot be safely accessed, consider another CT arrangement.
For more information, please visit our website.
A split core CT is an instrument transformer with a core that separates into sections so it can be placed around an existing conductor. The primary conductor passes through the core and acts as the CT’s primary winding, while the CT’s secondary winding provides a proportional current signal to a meter, monitor, or protection device. The split construction avoids having to thread a disconnected conductor through a closed core. Correct core closure and alignment are important because a gap or poor fit can affect measurement performance.
In an existing electrical system, a split core CT can add a current input to an energy meter, power monitoring system, building management system, or other compatible instrument. It can support load visibility, equipment monitoring, and energy-management activities when paired with suitable measurement equipment. It measures current rather than voltage, so voltage measurement and the associated system data require compatible, separately connected inputs. The CT does not reduce the load current flowing through the conductor.
Choose a split core design when the conductor is already terminated and removing it would require a larger shutdown or substantial panel work. This can be relevant in distribution boards, switchgear, motor control centers, and equipment cabinets where space and access are limited. A retrofit may still require an outage or safe isolation to open the enclosure and position the CT. “No conductor disconnection” should not be interpreted as “no electrical safety procedure.”
Split core CTs can be useful when monitoring several feeders or loads in an existing installation. Each CT must be installed on the intended conductor, with its orientation and secondary wiring arranged as specified by the manufacturer and connected instrument. For three-phase measurements, the measuring system must be configured to match the circuit and the number of CTs used. A qualified installer can confirm whether the monitoring device supports the proposed arrangement.
Where current measurement is needed for an audit, commissioning activity, or phased monitoring project, the ability to fit a CT around an installed conductor can simplify deployment. Check whether the selected model is intended for the planned duration and environment, and whether the measurement device can accept its output. Temporary use still requires appropriate access control, safe working practices, and secure secondary connections. Do not treat a removable CT as a substitute for a documented installation procedure.
A split core CT may not be the best choice where the required measurement accuracy is very high, the installation has severe space constraints, or the conductor cannot be safely reached. Some applications may be better served by a solid-core CT, a purpose-designed sensor, or a measurement system specified for the required performance. Performance depends on the particular CT, installation, connected burden, and instrument; split-core construction alone does not establish an accuracy level. Compare the manufacturer’s stated specifications with the project requirements rather than assuming all split core models perform alike.
SINAVA are exported all over the world and different industries with quality first. Our belief is to provide our customers with more and better high value-added products. Let's create a better future together.
Also check whether the system is intended for protection or revenue-grade measurement. Do not assume that a general monitoring CT is suitable for either purpose unless its ratings and documentation explicitly support the application. If the CT’s secondary is a conventional current output, observe its specified wiring and safety requirements. In particular, a conventional CT secondary must not be left open-circuit while primary current is flowing; follow the manufacturer’s instructions for safe connection, disconnection, and shorting arrangements.
Record the circuit type, normal operating current, expected maximum current, and the conductor to be measured. Select a primary-current rating and ratio that suit both the expected load and the connected instrument. Avoid choosing a ratio based only on a panel label if measured operating conditions are available. Confirm that the selected range provides usable readings for the load levels that matter to your project.
Check whether the receiving device requires a current output, such as 1 A or 5 A, or a low-voltage output such as millivolts. These are different interface types and are not interchangeable without compatible equipment. For current-output CTs, verify the permitted burden, including the meter input and wiring, against the CT documentation. For voltage-output sensors, confirm the specified input range and connection method of the monitor.
Measure the conductor dimensions and available clearance before selecting the aperture size. Include space to open and close the core and route the secondary leads without putting strain on the enclosure or conductors. Verify the system voltage, frequency, insulation rating, and environmental conditions against the product data. For example, a SINAVA 0.66 kV split core current transformer should be evaluated against the specific circuit and installation requirements, not selected solely because the nominal voltage appears suitable.
| Selection item | What to verify | Why it matters |
|---|---|---|
| Primary rating and ratio | Expected current range and instrument settings | Helps ensure readings suit the intended monitoring range |
| Output and burden | Current or voltage output, meter compatibility, and wiring load | Prevents an incompatible CT-to-instrument connection |
| Aperture and installation | Conductor size, clearance, core closure, and access | Confirms that the CT can be fitted and secured correctly |
| Electrical and environmental ratings | Voltage, frequency, insulation, and operating conditions | Supports suitability for the actual installation environment |
Before installation, identify the circuit, confirm the isolation and access requirements, and review the CT and instrument instructions. Have a qualified person position the CT around the correct conductor, close and secure the core, and connect the secondary as specified. After installation, verify polarity, phase association, instrument configuration, and plausible readings using the project’s commissioning process. If readings are unexpected, check the ratio setting, conductor placement, core closure, wiring, and connected-device compatibility.
For B2B projects, share the circuit voltage and frequency, expected primary current, required output, connected instrument model, conductor dimensions, installation environment, and quantity when requesting a split core CT recommendation. This information helps SINAVA assess product fit and identify specification details that need confirmation before quotation. If the project involves a 0.66 kV split core current transformer, include the relevant system conditions rather than relying on voltage alone. Request the applicable product datasheet and installation guidance for the model under consideration.
Use a split core current transformer when you need to add current measurement to an existing electrical system and opening the CT around an installed conductor is more practical than removing the conductor for a solid-core design. Before proceeding, confirm that the selected CT matches the current range, secondary interface, burden, physical clearance, system voltage, and measurement purpose. Have a qualified professional review the installation and follow the manufacturer’s safety instructions, especially for secondary connections. The next step is to document your circuit and instrument requirements, then ask SINAVA to help confirm a suitable model and its specifications.